2. INSTALLATION AND WIRING
2.6 Control circuit
Downloaded from
ManualsNet.com
Terminal name
Turn ON the STF signal to start
Forward rotation
forward rotation and turn it OFF to
start
stop.
Turn ON the STR signal to start
Reverse rotation
reverse rotation and turn it OFF to
start
stop.
Start self-holding
Turn ON the STP (STOP) signal to self-hold the start
selection
signal.
Multi-speed
Multi-speed can be selected according to the
selection
combination of RH, RM and RL signals.
Turn ON the JOG signal to enable JOG operation
Jog mode selection
(initial setting) and turn ON the start (STF or STR)
signal to start JOG operation.
Terminal JOG is also used as a pulse train input
terminal. To use as a pulse train input terminal, change
Pulse train input
the Pr.291 setting.
(maximum input pulse: 100k pulses/s)
Turn ON the RT signal to enable the second function.
Second function
When the second function such as "Second torque
selection
boost" and "Second V/F (base frequency)" is set,
turning ON the RT signal enables the selected function.
Turn ON the MRS signal (20 ms or more) to stop the
inverter output. Use this signal to shut off the inverter
Output stop
output when stopping the motor with an
electromagnetic brake.
Use this signal to reset a fault output provided when a
protective function is activated. Turn ON the RES
signal for 0.1 second or longer, then turn it OFF.
Reset
In the initial setting, reset is always enabled. By setting
Pr.75, reset can be enabled only at an inverter fault
occurrence. The inverter recovers about 1 second after
the reset is released.
The terminal 4 function is available only when the AU
Terminal 4 input
signal is ON.
selection
Turning the AU signal ON makes terminal 2 invalid.
Selection of
When the CS signal is left ON, the inverter restarts
automatic restart
automatically at power restoration. Note that restart
after instantaneous
setting is necessary for this operation. In the initial
power failure
setting, a restart is disabled.
search engine
Terminal function description
When the STF
and STR signals
are turned ON
simultaneously,
the stop
command is
given.
Refer
Rated specification
to
page
722
Input resistance: 4.7
kΩ,
voltage when contacts
are open: 21 to 27
722
VDC,
current when contacts
are short-circuited: 4 to
411
6 mADC
410
Input resistance: 2 kΩ,
current when contacts
406
are short-circuited: 8 to
13 mADC
525
524
Input resistance: 4.7
kΩ,
voltage when contacts
are open: 21 to 27
VDC,
336
current when contacts
are short-circuited: 4 to
6 mADC
496
628,
635