Mitsubishi Electric FR-A800 Series Instruction Manual page 449

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Monitor item
*7*18
Output voltage
Fault indication
Set frequency / motor
speed setting
Operation speed
Motor torque
Converter output
*7
voltage
Regenerative brake
*8
duty
Electronic thermal O/
L relay load factor
Output current peak
*7
value
Converter output
*7
voltage peak value
Input power
*9
Output power
Load meter
Motor excitation
*7
current
*11
Position pulse
Cumulative
*3
energization time
*11
Orientation status
Actual operation
*3*4
time
Motor load factor
*7
Cumulative energy
Position command
(lower digits)
Position command
(upper digits)
448
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Downloaded from
ManualsNet.com
Increment
Pr.
RS-485
and unit
setting
0.1 V
3/0/100 H03
0/100
*17
*2
H05
0.01 Hz
5
*2
1 (r/min)
H06
6
*2
0.1%
H07
7
*2
0.1 V
H08
8
*2
0.1%
H09
9
*2
0.1%
H0A
10
*6
*2
H0B
0.01/0.1 A
11
*2
0.1 V
H0C
12
*6
*2
H0D
0.01/0.1 kW
13
*6
*2
H0E
0.01/0.1 kW
14
0.1%
17
H11
*6
18
H12
0.01 A/0.1 A
19
H13
1h
20
H14
1
22
H16
1 h
23
H17
0.1%
24
H18
0.01/0.1
25
H19
*5*6
kWh
1
26
H1A
1
27
H1B
search engine
Negative
MODBUS
indication
RTU
*1
(-)
40203
The inverter output voltage is displayed.
Each of the last 8 faults is displayed individually.
40205
The set frequency is displayed.
The motor speed is displayed (depending on the settings
of Pr.37 and Pr.144). (Refer to
*21
40206
During encoder feedback control operation or under
Vector control, the actual motor speed according to
encoder signals is displayed.
The motor torque is displayed as a percentage (0%
40207
under V/F control), considering the rated torque as
100%.
40208
The DC bus voltage value is displayed.
Brake duty set in Pr.70 for the regeneration unit set in
40209
Pr.30 is displayed.
The motor thermal cumulative value is displayed,
40210
considering the thermal operation level as 100%.
The peak value of output current, which is constantly
40211
stored, is displayed. (It is reset with every startup of the
inverter.)
The DC bus voltage peak value, which is constantly
40212
stored, is displayed. (It is reset with every startup of the
inverter.)
40213
The power at the inverter input side is displayed.
40214
The power at the inverter output side is displayed.
Torque current is displayed as a percentage, considering
Pr.56 setting value as 100% (considering the motor rated
40217
torque as 100% under Real sensorless vector control or
Vector control).
40218
The motor excitation current is displayed.
The number of pulses per motor rotation during
orientation control operation or in the position control
40219
mode is displayed. (The output voltage is displayed when
a Vector control option is not installed.)
The cumulative energization time since the inverter
shipment is displayed. The number of times an
40220
integrated value has reached the maximum value of
65535 hours can be checked in Pr.563.
Monitoring is enabled only during orientation control
operation. (The output voltage is displayed when a
40222
Vector control option is not installed.) (Refer to
585.)
The cumulative operation time is displayed. The number
of times an integrated value has reached the maximum
40223
value of 65535 hours can be checked in Pr.564. Use
Pr.171 to reset the cumulative operation time. (Refer to
page
454.)
The output current value is displayed as a percentage,
considering the inverter rated current value as 100%.
40224
Readout (%) = present output current value / inverter
rated current value × 100
The cumulative energy based on the monitored output
40225
power is displayed. Use Pr.170 to reset it. (Refer to
454.)
40226
The position command (decimal) before the electronic
gear is set is displayed.
40227
Description
page
444.)
page
page
*10