Mitsubishi Electric FR-A800 Series Instruction Manual page 524

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Setting
66
X66
67
X67
68
NP
69
CLR
70
X70
71
X71
72
X72
73
X73
74
X74
76
X76
77
X77
78
X78
79
X79
80
X80
85
X85
87
X87
88
LSP
89
LSN
92
X92
93
X93
94
X94
95
X95
96
X96
128
RLF
129
RLR
9999
-
*1
When Pr.59 Remote function selection ≠ "0", functions of the RL, RM, and RH signals are changed as shown in the table.
*2
When Pr.270 Stop-on contact/load torque high-speed frequency control selection = "1, 3, 11, or 13", functions of the RL and RT signals are
changed as shown in the table.
*3
The OH signal is activated when the relay contact is open.
*4
When a stop position command is input from outside for orientation control, the FR-A8AX (16-bit digital input option) is required.
*5
Servo ON is enabled in the position control mode.
*6
Available when the plug-in option is connected. For details, refer to the Instruction Manual of each option.
*7
The setting is available for the standard structure model and the IP55 compatible model.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• The priorities of the speed commands are defined as follows: JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the Inverter run enable (X10) signal is not assigned, or when the PU operation external interlock (X12) signal is not
assigned while Pr.79 Operation mode selection = "7", the MRS signal performs the same function.
• The same terminals are used to assign the multi-speed (7-speed) setting and the remote setting. The multi-speed setting and
the remote setting cannot be assigned separately.
• When the Load pattern selection forward/reverse rotation boost (X17) signal is not assigned, the RT signal performs the same
function.
• When Pr.419 = "2" (simple pulse train position command), the terminal JOG is used for the simple position pulse train input
regardless of the setting in Pr.291 Pulse train I/O selection.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
Downloaded from
ManualsNet.com
Signal
name
External/NET operation switchover (NET operation with X66-ON)
Command source switchover (command by Pr.338 or Pr.339
enabled with X67-ON)
Simple position pulse train sign
Simple position droop pulse clear
DC feeding operation permission
*7
DC feeding cancel
PID P control switchover
Second PID P control switchover
Magnetic flux decay output shutoff
Proximity dog
Pre-charge end command
Second pre-charge end command
Second PID forward/reverse action switchover
Second PID control valid
SSCNET III communication disabled (for FR-A8NS)
Sudden stop
Forward stroke end
Reverse stroke end
Emergency stop
Torque control selection
Control signal input for main circuit power supply MC
Converter unit fault input
Converter unit fault (E.OHT, E.CPU) input
Low-speed forward rotation command
Low-speed reverse rotation command
No function
search engine
Function
*7
*6
Related parameter
Pr.79, Pr.340
Pr.338, Pr.339
Pr.291, Pr.419 to Pr.430,
Pr.464
Pr.291, Pr.419 to Pr.430,
Pr.464
Pr.30
Pr.30
Pr.127 to Pr.134, Pr.575 to
Pr.577
Pr.127 to Pr.134, Pr.575 to
Pr.577
Pr.850
Pr.1282 to Pr.1288
Pr.760 to Pr.764
Pr.765 to Pr.769
Pr.753 to Pr.758
Pr.753 to Pr.758
Pr.499
Pr.464 to Pr.494
Pr.419
Pr.1103
Pr.1113
Pr.30, Pr.137, Pr.248, Pr.254
Pr.57, Pr.58, Pr.135 to
Pr.139, Pr.159
Pr.6
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Refer to
page
1
389
400
2
320
320
3
724
724
601
4
601
717
5
303
618
618
601
6
601
303
7
316,
319
367
287
8
569
563
9
411
10
523