Mitsubishi Electric FR-A800 Series Instruction Manual page 354

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 GOT initial setting (RS-485 terminals) (Pr.999 = "11, 13")
Pr.
79
Operation mode selection
332
RS-485 communication speed
RS-485 communication stop bit length / data
333
length
334
RS-485 communication parity check selection
335
RS-485 communication retry count
336
RS-485 communication check time interval
337
RS-485 communication waiting time setting
340
Communication startup mode selection
341
RS-485 communication CR/LF selection
414
PLC function operation selection
549
Protocol selection
*1
The setting is changed when Pr.414 = "0" (initial setting).
 Initial setting with the GOT2000 series
• When "FREQROL 500/700/800, SENSORLESS SERVO" is selected for "Controller Type" in the GOT setting, set Pr.999
= "11" to configure the GOT initial setting.
• When "FREQROL 800 (Automatic Negotiation)" is selected for "Controller Type" in the GOT setting, the GOT automatic
connection can be used. When "FREQROL 800 (Automatic Negotiation)" is selected for "Controller Type" in the GOT
setting and the GOT automatic connection is not used, set Pr.999 = "13" to configure the GOT initial setting. (Refer to
701.)
 Initial setting with the GOT1000 series
• Set Pr.999 = "11" to configure the GOT initial setting.
NOTE
• Always perform an inverter reset after the initial setting.
• For details on connection with GOT, refer to the Instruction Manual of GOT.
Downloaded from
ManualsNet.com
Name
search engine
Initial value
Pr.999 = "11"
0
0
96
192
1
10
2
1
1
9999
0 s
9999
9999
0 ms
0
1
1
1
0
0
0
Pr.999 = "13"
Refer to page
0
389
1152
0
1
670
9999
9999
0 ms
1
398
1
670
*1
646
2
0
686
5. PARAMETERS
5.7 (E) Environment setting parameters
1
2
3
4
5
6
7
page
8
9
10
353