• The droop control and the speed loop integration at the emergency stop by the Emergency stop (X92) signal can be
enabled/disabled using Pr.1349 Emergency stop operation selection.
Pr.1349
setting
0
Enabled
1
Enabled
10
Disabled
11
Disabled
NOTE
• The X92 signals can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• Refer to
• Refer to
Parameters referred to
Pr.3 Base
frequencypage 707
Pr.10 DC injection brake operation
Pr.29 Acceleration/deceleration pattern
Pr.125, Pr.126 (frequency setting gain
Pr.178 to Pr.189 (Input terminal function
Pr.264 Power-failure deceleration time 1, Pr.265 Power-failure deceleration time
5.8.2

Acceleration/deceleration pattern

The acceleration/deceleration pattern can be set according to the application. In addition, the backlash measures that stop
acceleration/deceleration by the frequency or time set with parameters at acceleration/deceleration can be set.
Pr.
29
Acceleration/deceleration pattern
F100
selection
140
Backlash acceleration stopping
F200
frequency
141
Backlash acceleration stopping
F201
time
142
Backlash deceleration stopping
F202
frequency
143
Backlash deceleration stopping
F203
time
380
Acceleration S-pattern 1
F300
381
Deceleration S-pattern 1
F301
382
Acceleration S-pattern 2
F302
383
Deceleration S-pattern 2
F303
516
S-pattern time at a start of
F400
acceleration
517
S-pattern time at a completion of
F401
acceleration
518
S-pattern time at a start of
F402
deceleration
519
S-pattern time at a completion of
F403
deceleration
372
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Downloaded from
ManualsNet.com
Description
Droop control
Enabled
Disabled
Enabled
Disabled
page 738
for details on the droop control.
page 254
for details on the speed loop integration.
frequencypage 715
selectionpage 372
frequency)page 505
selection)page 521
Initial
Name
value
0
1 Hz
0.5 s
1 Hz
0.5 s
0
0
0
0
0.1 s
0.1 s
0.1 s
0.1 s
search engine
Speed loop integration
2page 505
Setting range
0
Linear acceleration/deceleration
1
S-pattern acceleration/deceleration A
2
S-pattern acceleration/deceleration B
3
Backlash measure
4
S-pattern acceleration/deceleration C
5
S-pattern acceleration/deceleration D
6
Variable-torque acceleration/deceleration
0 to 590 Hz
0 to 360 s
Set the stopping frequency and time during backlash
measures.
Valid by backlash measures (Pr.29 = "3").
0 to 590 Hz
0 to 360 s
0 to 50%
Set the time for drawing the S-pattern from acceleration/
deceleration start to linear acceleration as a ratio (%) of
0 to 50%
acceleration/deceleration time (Pr.7, 8, etc.). The
acceleration/deceleration curve can be switched by the X20
0 to 50%
signal.
Valid by S-pattern acceleration/deceleration C (Pr.29 = "4").
0 to 50%
0.1 to 2.5 s
0.1 to 2.5 s
Set the time required for acceleration (S-pattern) of S-
pattern acceleration/deceleration.
Valid by S-pattern acceleration/deceleration D (Pr.29 = "5").
0.1 to 2.5 s
0.1 to 2.5 s
Description