Mitsubishi Electric FR-A800 Series Instruction Manual page 651

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Pr.
1020
Trace operation selection 0
A900
1021
Trace mode selection
A901
1022
Sampling cycle
A902
1023
Number of analog
A903
channels
1024
Sampling auto start
A904
1025
Trigger mode selection
A905
1026
Number of sampling
A906
before trigger
1027
Analog source selection
A910
(1ch)
1028
Analog source selection
A911
(2ch)
1029
Analog source selection
A912
(3ch)
1030
Analog source selection
A913
(4ch)
1031
Analog source selection
A914
(5ch)
1032
Analog source selection
A915
(6ch)
1033
Analog source selection
A916
(7ch)
1034
Analog source selection
A917
(8ch)
1035
Analog trigger channel
A918
1036
Analog trigger operation
A919
selection
1037
Analog trigger level
A920
650
5. PARAMETERS
5.14 (A) Application parameters
Downloaded from
ManualsNet.com
Name
Initial value
0
2
4
0
0
90%
201
202
203
204
205
206
207
208
1
0
1000
search engine
Setting
range
0
Without trace operation (The read value is always "0".)
1
Sampling start
2
Forced trigger
3
Sampling stop
4
Transfer of data to USB memory device
0
Memory mode
1
Memory mode (automatic transfer)
2
Recorder mode
Set the sampling cycle.
0: approx. 0.125 ms, 1: approx. 0.25 ms, 2: 1 ms, 3: 2 ms, 4: 5 ms,
0 to 9
5: 10 ms, 6: 50 ms, 7: 100 ms, 8: 500 ms, 9: 1 s
(For the setting values "0" and "1", the cycle varies according to the
control mode.)
1 to 8
Select the number of analog channels for sampling.
0
Manual sampling start
Sampling starts automatically when the power supply is turned ON
1
or at a reset
0
Fault trigger
1
Analog trigger
2
Digital trigger
3
Analog or digital trigger (OR logic)
4
Both analog and digital triggers (AND logic)
Set the percentage of the pre-trigger sampling time with respect to
0 to 100%
the overall sampling time.
1 to 3, 5 to
14, 17 to 20,
22 to 24, 32
to 36, 39 to
42, 46, 52 to
54, 61, 62,
Select the analog data (monitor item) for sampling on each channel.
64, 67, 71 to
75, 87 to 98,
201 to 213,
222 to 227,
230 to 232,
235 to 238
1 to 8
Select the analog channel to be the trigger.
Sampling starts when the value of the analog monitor exceeds the
0
value set at the trigger level (Pr.1037)
Sampling starts when the value of the analog monitor falls below the
1
value set at the trigger level (Pr.1037)
Set the level at which the analog trigger turns ON.
600 to 1400
The trigger level is the value obtained by subtracting 1000 from the
set value.
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents