 Instructions for encoder cable wiring
• Use shielded twisted pair cables (0.2 mm
several cables in parallel or use a thick cable, according to the wiring length.
To protect the cables from noise, run them away from any source of noise (such as the main circuit and power supply
voltage).
Wiring length
Within 10 m
Within 20 m
*1
Within 100 m
*1
When differential line driver is set and a wiring length is 30 m or more.
The wiring length can be extended to 100 m by increasing the 5 V power supply (approximately to 5.5 V) while using six or more 0.2 mm
cables in parallel or a 1.25 mm
• To reduce noise of the encoder cable, earth (ground) the encoder's shielded cable to the enclosure (as close as possible
to the inverter) with a metal P-clip or U-clip.
• When one encoder is shared between the FR-A8AP and CNC (computerized numerical controller), its output signal should
be connected as follows. In this case, the wiring length between the FR-A8AP and CNC should be as short as possible,
within 5 m.
NOTE
• For details on the optional encoder dedicated cable (FR-JCBL/FR-V7CBL), refer to
• The FR-V7CBL is provided with a P-clip for earthing (grounding) shielded cables.
Downloaded from
ManualsNet.com
2
(with complementary encoder output)
FR-A800
(FR-A8AP)
Parallel connection
At least two cables in parallel
At least four cables in parallel
At least six cables in parallel
2
or larger gauge cable. The voltage applied must be within power supply specifications of encoder.
Earthing (grounding) example using a P-clip
Inverter
(FR-A8AP)
Maximum 5 m
(two parallel cables)
search engine
or larger) to connect the FR-A8AP. For the wiring to terminals PG and SD, use
Example of parallel connection
with two cables
Encoder
PA1
A
PA2
B
FB1
C
FB2
D
PZ1
F
PZ2
G
PG
S
R
SD
2
2 mm
PG
SD
Larger-size cable
0.4 mm
Wire gauge 0.2
0.75 mm
2
mm
1.25 mm
Encoder cable
Shield
P-clip
Encoder
CNC
2.8 Connection to a motor with encoder (Vector control)
2
or larger
2
or larger
2
or larger
page
89.
2. INSTALLATION AND WIRING
1
2
3
4
5
6
7
8
2
gauge
9
10
93