Starting Frequency And Start-Time Hold Function - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

• When the remotely-set frequency is cleared by turning ON the clear (RL) signal after turning OFF (ON) both the RH and RM
signals, the inverter operates at the frequency in the remotely-set frequency cleared state if power is reapplied before one
minute has elapsed since turning OFF (ON) both the RH and RM signals.
CAUTION
• When using the remote setting function, set the maximum frequency again according to the machine.
Parameters referred to
Pr.1 Maximum frequency, Pr.18 High speed maximum
Pr.7 Acceleration time, Pr.8 Deceleration time, Pr.44 Second acceleration/deceleration time, Pr.45 Second deceleration
Pr.28 Multi-speed input compensation
Pr.178 to Pr.189 (Input terminal function
5.8.4
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
It is possible to set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when a starting torque is needed or the motor drive at start needs smoothing.
Pr.
13
Starting frequency
F102
571
Holding time at a start
F103
 Starting frequency setting (Pr.13)
• The frequency at start can be set in the range of 0 to 60 Hz.
• Set the starting frequency at which the start signal is turned ON.
Output
frequency
(Hz)
60
Pr.13
0
STF
NOTE
• The inverter does not start if the frequency setting signal has a value lower than that of Pr.13.
For example, while Pr.13 = 5 Hz, the inverter output starts when the frequency setting signal reaches 5 Hz.
 Start-time hold function (Pr.571)
• This function holds during the period set in Pr.571 and the output frequency set in Pr.13 Starting frequency.
Downloaded from
ManualsNet.com
Remotely-set frequency stored last time
Acceleration (RH)
Deceleration (RM) OFF
Clear (RL)
Forward rotation (STF)
Power supply
selectionpage 411
selection)page 521

Starting frequency and start-time hold function

Sensorless Vector
Sensorless
Vector
Vector
Name
Initial value
0.5 Hz
9999
Time
ON
search engine
One minute
More than
one minute
ON
ON
ON
ON
frequencypage 428
Setting range
Set the starting frequency at which the start signal is turned
0 to 60 Hz
ON.
0 to 10 s
Set the holding time of the frequency set in Pr.13.
9999
The holding function at start is disabled.
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Operation is performed at the set
frequency 0Hz.
Time
ON
ON
timepage 367
Description
1
2
3
4
5
6
7
8
9
10
381
5. PARAMETERS