 Adjustment by changing the torque without adjusting the voltage (current) (Example of
changing the gain torque from 150% to 130%)
Operating procedure
1.
Selecting the parameter
Turn
Press
2.
Torque setting change
Turn
Press
3.
Selecting the mode and the monitor item
Press
4.
Start
Turn ON the start switch (STF or STR) to apply a voltage across terminals 1 and 5 (4 and 5),
Operation is performed with 130% torque.
NOTE
• If the voltage (current) values at the gain and bias torques are too close to each other, an error ("
indicated.
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• Use the calibration parameter C16 (Pr.919) or C38 (Pr.932) to set the bias torque. (Refer to
CAUTION
• Be cautious when setting any value other than "0" as the bias torque at 0 V (0 mA). Even if a torque command is not
given, simply turning ON the start signal will supply torque to the motor.
Parameters referred to
Pr.20 Acceleration/deceleration reference
Pr.73 Analog input selection, Pr.267 Terminal 4 input
Pr.79 Operation mode
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function
516
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Downloaded from
ManualsNet.com
until "
" (Pr.920) appears for terminal 1, or "
to read the present set value. (150.0%)
to change the set value to "
to confirm the selection. "
three times to select the monitor mode, and change the monitor item to the frequency.
frequencypage 367
selectionpage 496
selectionpage 389
search engine
" (130.0%)
" and "
" ("
assignmentpage 500
" (Pr.933) for terminal 4.
") are displayed alternately.
page
512.)