• By setting "3, 13, 1003, or 1013" in Pr.162, the restart can be made smoother with even less impact than when "0, 10,
1000, or 1010" is set in Pr.162. When the inverter is restarted with "3, 13, 1003, or 1013" set in Pr.162, offline auto tuning
is required. (For details on offline auto tuning of Advanced magnetic flux vector control and Real sensorless vector control,
refer to
page
532, and for details on offline auto tuning of V/F control, refer to
V/F control, Advanced magnetic flux vector control
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Inverter output
voltage E(V)
Coasting
+
time (Pr.57)
* The output shut off timing differs
according to the load condition.
NOTE
• The rotation speed detection time (frequency search) changes according to the rotation speed of the motor. (maximum 1 s)
• When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent protective function (E.OC[]) is
sometimes activated and prevents the inverter from restarting.
• If two or more motors are connected to one inverter, this function operates abnormally. (The inverter does not restart
successfully.)
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• If reverse operation is detected when "1" (reverse rotation disabled) is set to Pr.78, operation decelerates by reverse rotation
and then changes to forward rotation when the start command is forward rotation. The inverter does not restart when the start
command is reverse rotation.
• When "3, 13, 1003, or 1013" is set to Pr.162, limit the wiring length to within 100 m.
 Restart operation without frequency search (Pr.162 ="1, 11, 1001, or
1011")
• When Pr.162 = "1 11, 1001, or 1011", reduced voltage start is used for the restart operation. In this method, the voltage is
raised gradually while keeping the output frequency level at the level before an instantaneous power failure, regardless of
the motor's coasting speed.
V/F control, Advanced magnetic flux vector control
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Inverter output
voltage E(V)
Coasting time
Pr.57 setting
* The output shut off timing differs according to the load condition.
632
5. PARAMETERS
5.14 (A) Application parameters
Downloaded from
ManualsNet.com
Instantaneous (power failure) time
*
Restart cushion
Speed
time (Pr.58 setting)
detection
time
Acceleration time
at a restart
(Pr.611 setting)
Instantaneous (power failure) time
*
Restart cushion time
(Pr.58 setting)
search engine
page
638.)
Real sensorless vector control
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
*
output voltage
E(V)
Speed
Coasting
detection
+
time (Pr.57)
time
* The output shut off timing differs
according to the load condition.
Acceleration time
at a restart
(Pr.611 setting)