• Example of operation sequence with automatic bypass sequence (Pr.139 ≠ "9999", Pr.159 ≠ "9999")
STF
Output frequency Pr.139
Frequency command
Actual motor speed
INV
MC3
operation
Commercial
MC2
power supply
operation
A : Pr.136 MC switchover interlock time
C : Pr.57 Restart coasting time
Operating procedure
• Operation flowchart
Power supply ON
Setting the parameters
Start inverter operation
Constant-speed commercial
power supply operation
Deceleration (stop)
inverter operation
• Signal operation after setting parameters
Status
Power ON
At start
(inverter)
During constant-speed
operation
(commercial power supply)
Switching to inverter
operation due to
deceleration (inverter)
Stop
Downloaded from
ManualsNet.com
ON
OFF
ON
OFF
ON
OFF
C
A
• Pr.135 = "1"
• Pr.136 = 2.0 s
• Pr.137 = 1.0 s (Set the time until MC3 is actually turned ON and the inverter and motor
are electrically connected. If the time is short, the restart may not function properly.)
• Pr.57 = 0.5 s
• Pr.58 = 0.5 s (Always set this to switchover from the commercial power supply operation
to the inverter operation.)
MRS
CS
OFF
OFF
(OFF)
(OFF)
OFF→ON OFF→ON OFF→ON ON
ON
ON→OFF ON
ON
OFF→ON ON
ON
ON
search engine
Pr.159
A
B
C
D
A
B : Pr.137 Start waiting time
D : Pr.58 Restart cushion time
STF
MC1
MC2
OFF
OFF→ON
OFF
(OFF)
(OFF→ON)
(OFF)
OFF
ON
OFF→ON ON→OFF
ON
ON→OFF OFF→ON
ON→OFF ON
OFF
A
B
C
D
MC3
Remarks
OFF → ON
External operation mode (PU
(OFF →
operation mode)
ON)
ON
MC2 turns ON after MC3 turns OFF.
The delay time is 2 s (while
coasting).
MC3 turns ON after MC2 turns OFF.
The delay time is 4 s (while
coasting).
ON
5. PARAMETERS
5.14 (A) Application parameters