Mitsubishi Electric FR-A800 Series Instruction Manual page 606

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 Connection diagram
• Sink logic
• Pr.128 = 20
• Pr.183 = 14
• Pr.191 = 47
• Pr.192 = 16
• Pr.193 = 14
• Pr.194 = 15
*1
Prepare a power supply matched to the power supply specifications of the detector.
*2
The applied output terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3
The applied input terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection)
*4
The AU signal need not be input.
 Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
Downloaded from
ManualsNet.com
Power supply
Forward
rotation
Reverse
rotation
PID control
selection
Setting
Potentiometer
(Set point setting)
AC1φ
200/220V 50/60Hz
search engine
Inverter
MCCB
R/L1
U
S/L2
V
T/L3
W
STF
STR
RT(X14)
∗3
∗2
(PID)SU
SD
∗2
(FUP)FU
(FDN)OL
∗2
10
2
∗2
(RL)IPF
5
1
SE
Output signal common
∗4
4
(Measured value) 4 to 20mA
0 24V
Power
∗1
supply
Pump
Motor
M
P
2-wire type
3-wire
During PID action
type
Detector
Upper limit
Lower limit
-
-
+
+
Forward rotation
output
Reverse rotation
output
(OUT)
(COM)
5. PARAMETERS
5.14 (A) Application parameters
1
2
3
4
+
(24V)
5
6
7
8
9
10
605