Master Transmitter Mode; User Manual - Philips LPC2101 User Manual

Table of Contents

Advertisement

Philips Semiconductors
Volume 1
Table 129: Abbreviations used to describe an I
Abbreviation
A
A
Data
P
In
The numbers in the circles show the status code held in the I2STAT register. At these
points, a service routine must be executed to continue or complete the serial transfer.
These service routines are not critical since the serial transfer is suspended until the serial
interrupt flag is cleared by software.
When a serial interrupt routine is entered, the status code in I2STAT is used to branch to
the appropriate service routine. For each status code, the required software action and
details of the following serial transfer are given in tables from

11.8.1 Master Transmitter mode

In the master transmitter mode, a number of data bytes are transmitted to a slave receiver
(see
initialized as follows:
Table 130: I2CONSET used to initialize Master Transmitter mode
The I
set to logic 1 to enable the I
acknowledge its own slave address or the general call address in the event of another
device becoming master of the bus. In other words, if AA is reset, the I
enter a slave mode. STA, STO, and SI must be reset.
The master transmitter mode may now be entered by setting the STA bit. The I
now test the I
When a START condition is transmitted, the serial interrupt flag (SI) is set, and the status
code in the status register (I2STAT) will be 0x08. This status code is used by the interrupt
service routine to enter the appropriate state service routine that loads I2DAT with the
slave address and the data direction bit (SLA+W). The SI bit in I2CON must then be reset
before the serial transfer can continue.
When the slave address and the direction bit have been transmitted and an
acknowledgment bit has been received, the serial interrupt flag (SI) is set again, and a
number of status codes in I2STAT are possible. There are 0x18, 0x20, or 0x38 for the
master mode and also 0x68, 0x78, or 0xB0 if the slave mode was enabled (AA = logic 1).
The appropriate action to be taken for each of these status codes is detailed in
After a repeated start condition (state 0x10). The I
receiver mode by loading I2DAT with SLA+R).

User manual

Explanation
Acknowledge bit (LOW level at SDA)
Not acknowledge bit (HIGH level at SDA)
8-bit data byte
Stop condition
Figure 32
to
Figure
36, circles are used to indicate when the serial interrupt flag is set.
Figure
32). Before the master transmitter mode can be entered, I2CON must be
Bit
7
6
Symbol
-
I2EN
Value
-
1
2
C rate must also be configured in the I2SCLL and I2SCLH registers. I2EN must be
2
C-bus and generate a start condition as soon as the bus becomes free.
Rev. 01 — 12 January 2006
2
C operation
5
4
3
STA
STO
SI
0
0
0
2
C block. If the AA bit is reset, the I
2
C block may switch to the master
UM10161
2
Chapter 11: I
C interfaces
Table 133
to
Table
137.
2
1
0
AA
-
-
x
-
-
2
C block will not
2
C interface cannot
2
C logic will
Table
© Koninklijke Philips Electronics N.V. 2006. All rights reserved.
133.
133

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lpc2103Lpc2102

Table of Contents