Toshiba GR200 Series Instruction Manual page 114

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.3.5
Setting of CBP_FS (Function ID: 48CB01)
Setting item
UVFS-EN
UV
UVFS
UVSFS-EN
UVS
UVSFS
UVDFS-EN
UVD
UVDFS
TUVDFS
Unit
Range
s
Off / On
Fail safe UVFS enable
5.0 - 130.0
V
UVFS relay operating value
Off / On
Fail safe UVSFS enable
5.0 - 130.0
V
UVSFS relay operating value
Off / On
Fail safe UVDFS enable
1 – 20
V
UVDFS relay operating value
0.00 - 300.00
s
Extended time of UVDFS operation
- 100 -
Default setting
Contents
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Notes
value
On
46.0
On
80.0
On
5
10.10

Hide quick links: