Select logic for resetting LEDs
3.6.1
The user should set scheme switch [LEDDR1] to On prior to the LEDR operation. Figure 3.6-1
shows selection logic in the LEDR function.
Wait for a command
Select logic
Resetting LED by remote-SAS
Signal reception
IEC61850
Figure 3.6-1 Outline of selection command for resetting LEDs
Input signal required mapping
(i)
Figure 3.6-2 shows the select logic when a "Select command (reset)" signal is applied to the
LEDR function. The logic has an input-point "LEDR01_CONTROL_REQ" for the reception;
the input-point must be mapped for IEC61850 communication. The function will fail to operate
if mapping is not performed correctly. We will discuss how to map the input points for the
IEC61850 communication in section 3.6.5.
Input
Command "Reset"
528001 7007016D08
LEDR01_CONTROL_REQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Logic '0' signal (Always Low (FALSE))
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 3.6-8.
*Note: The LEDR function can run on either "the SBO mode" or "the DIR mode" using a
"ctlmodel" signal when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
Output signal required mapping
(ii)
The LEDR
"LEDR01_NSD_CSF", when the LEDR function determines that the input signal "Select
Selection logic
Selection logic in LEDR
LEDR function (Function ID: 528001)
For SBO operation
Selection
command
For DIR operation
Operation
command
In SBO operation
In DIR operate
Select condition‡
Figure 3.6-2 Selection logic for resetting LEDs
function can issue a
Failed
Select
Signal output
decision
Success
LEDR01_FSE_RCV
(528001 8007011F42)
1≥
&
&
&
0
t
0.2s
0
t
0.3s
"Select success" signal at the output point
- 206 -
6F2S1931 (0.20)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
Output
LEDR01_NSD_CSF
To "Wait for a next command"
(528001 8307011F41)
528001 0007011001
LEDR01_STSELD
Failed
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)