Toshiba GR200 Series Instruction Manual page 546

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting of HOTST(Function ID: 341001)
Setting item
UpTime
Setting of Net_MONITOR (Function ID: 351001)
Setting item
NetMonitor_EN
Ping_IP1
Ping_IP2
Ping_IP3
Ping_IP4
Ping_IP5
Ping_IP6
Net
Monitor
Ping_IP7
Ping_IP8
Ping_IP9
Ping_IP10
Ping_IP11
Ping_IP12
Ping_Wait
Ping
Ping_Interval
Chk_Count
Range
Units
0 – 10000
ms
Determination time for link-up
Range
Units
Off / On
Enable switch for net monitoring
0 – 255
Ping address of first target
0 – 255
Ping address of second target
0 – 255
Ping address of third target
0 – 255
Ping address of forth target
0 – 255
Ping address of fifth target
0 – 255
Ping address of sixth target
0 – 255
Ping address of seventh target
0 – 255
Ping address of eighth target
0 – 255
Ping address of ninth target
0 – 255
Ping address of tenth target
0 – 255
Ping address of eleventh target
0 – 255
Ping address of twelfth target
1 – 10
sec
Ping packet waiting time
1 – 120
sec
Ping packet interval time
1 – 10
sec
Number of ping check count
- 532 -
Contents
Default setting value
Contents
Default setting value
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Notes
5
Notes
Off
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
0.0.0.0
1
5
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents