Toshiba GR200 Series Instruction Manual page 542

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

IP setting example [RedundantMode] =PRP or HSR
(vi)
When PRP or HSR is set for the setting [RedundantMode], the user can apply single IP address
in the IED. The table shows that Port A and B have the same IP address.
Table 10.2-6 Default IP address for PRP or HSR
Protocol
IEC61850(GOOSE)
IP address at
Port A†
192.168.1.11
IP address at
Port B†
IP address
Not applicable
for Local PC
†Note: Address '192.168.1.11' is set as default. Either port A or B is allowed to operate.
‡Note: '192.168.1.13' can be set for the local engineering PC, if LAN for Local PC is
mounted at C13.
SNTP
192.168.1.11
Not applicable
- 528 -
6F2S1931 (0.20)
GR-TIEMS® /
MULTIPLOG®
192.168.1.11
192.168.1.13‡
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)