Supervision of setting data (Setting error)
9.2.11
The values of the Settings are checked every second; the error message is displayed when the
erroneous value is found.
Error level
(i)
The error level has been set at level 1 (Serious error
carried out periodically. If the error is detected, the IED does not try to restart its operation
automatically. The function runs for the saved settings in the CPU module
erroneous setting is removed, the error messages will be cleared in a second.
Note: The CPU module is discussed in Chapter
1
and communication module: Processing module.
Error message
(ii)
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 9.2-22 Error messages provided by the supervisor in CHK_SETTING
Message and level
CP*_ (Setting) error
Error level
Table 9.2-23 Detailed information expressed in Hexadecimal in CHK_SETTING
Display
area
00000001: Failure exists in the common settings
Top
00000002: Failure exists in the group setting
row
00000004: Error data found in the setting table
Middle
Offset address corresponding to the failure in
row
the group setting
Bottom
(No information is displayed)
row
Meaning of the information
Setting error detected on the following module instructed with
"CP*_" as follows:
CP1M:
CPU module
Serious error (Level 1)
Meaning of the detailed information
Left column
- 478 -
) for the supervision; the detection is
1
Technical description: Signal processing
Right column
Offset address corresponding to
the failure in the common settings
Error information about the
setting table
(No information is displayed)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)