How to map IED signals to Modbus addresses
10.5.9
The Figure 10.5-12 is illustrated in order that an IED signal was connected for a Modbus
address, so the user has to map a Data ID for a Modbus address on the Modbus slave screen;
the operation the drag & drop on the screen. The function and data length (see Table 10.5-2)
is dependent on the Modbus address; thus, the user has to map signals based on the types of
the signals (Data IDs).
Select MODBUS tool on the Configuration tool, as shown in Figure 10.5-21; and then, the user
can edit a configuration file.
Selection of Modbus tool
Figure 10.5-21 Choice of Modbus engineering tool on GR-TIEMS
Note: We discuss the GR-TIMES operations for the Modbus mapping; hence, we use
1
some signals and addresses for the explanation of that. We omit the meanings of
applications signals.
Note: See the separate manual "
2
operation to change or erase addresses,
Operation manual GR-TIEMS (6F2M1082)
- 637 -
6F2S1931 (0.20)
" for the
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)