Toshiba GR200 Series Instruction Manual page 579

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Quality signal of IEC 61850 communication
10.3.7
Quality information and its attributes are defined in the IEC 61850. Table 10.3-6 shows that
the relations between the definitions in the standard and signals prepared in the IED. The
quality attributes are influenced by the errors and alarms occurred in the IED, and the degree
of those errors are standardized by settings 'Error level' (see Chapter
The quality information is also affected by the test mode executed in the IED (see Chapter
Commissioning and maintenance
Table 10.3-6 Quality signal defined in IEC 61850-7-3
Quality components definition in IEC 61850-7-3
Attribute Name
Validity
good / invalid / reserved / questionable
detailQual
overflow
2
outOfRange
2
badReference
oscillatory
2
Failure
oldData
2
inconsistent
2
Inaccurate
source
2
Test
operatorBlocked
2
Note: M/N/O means rules of attributions. If it is Mandatory (M), it shall be used in the
1
IED. Optionally (O), or conditional mandatory(C) are used depending on the
environment states.
Note: The IED does not carry those attributes—overflow, out Of Range, oscillatory, old
2
Data, inconsistent, source, and operator Blocked.
Note: Three kinds of default quality information are defined in the IEDs of GR200:
3
(i) U16_00
(ii) U16_01
(iii) Qual_Validity
The U16_00 (i) is a default quality signal and it has been mapped in logical nodes
(LNs). For actual mappings in the IED, see
PIXIT, and TICS
Some detail quality attributes (e.g., overflow, outOfRange, etc. marked with "N")
are not included.
).
Attribute value
packed value
(
)
process / substituted
True / False
True / False
Signal No. 230302 3112001BB0
Signal No. 230302 3112011BB0
Signal No. 301001 3110041005
. The user can find out the Quality attribute practically.
- 565 -
6F2S1931 (0.20)
Automatic supervision
M/
Default
O/
value
C
1
M
Undecided
(shall be
determined
depending
M
on an error
condition)
M
process
M
False
M
False
Appendix: IEC61850 MICS, PICS,
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
).
IED signals
3
Y
Y
Y
N
N
N
N
N
N
Y
N
N
N
N
N
Y
Y
N
N
N
N
N
N
N
N
Y
N
N
N
N
Y
Y
Y
N
N
N

Hide quick links: