Toshiba GR200 Series Instruction Manual page 652

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

[Type1] Mapping about Coil type
Figure 10.5-22 illustrates a mapping example for the Modbus Coil. In the figure,
signals (Data IDs) of the OC function are mapped for the Modbus address (00002).
The signal list screen allows the user chose signals on (Dragged); and then, the user
can release them on the Modbus Address screen (Dropped).
Modbus screen in detailed mode
Modbus address: 00002
IED Data ID (FID: 440081)
800001EBB0 OC1_BLOCK
PLC connection point (Data ID)
Figure 10.5-22 Example setting of Modbus Coil
Note: Logical Inverse is possible for signals when each check box is clicked. In the Detail
screen mode D, Period and Time adjusting values are screened, but they are used
for IED internal operations. Thus, the user does not have not set them.
4
The Coil type is R/W mode.
Detail info. of each address
Write Coil
Read Coil
8000011B23
OC1-OPT-TRIP
Signal monitoring point (Data ID)
- 638 -
Dropped
IED input point
Dragged
IED output point
IED signals (Data IDs)
Dragged
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)