Toshiba GR200 Series Instruction Manual page 538

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

IP setting example [RedundantMode]=Hot_standby
(vii)
When Hot_standby is set for the setting [RedundantMode], the user can apply single IP
address in the IED. The table shows that Port A and B have the same IP address.
Table 10.2-4 Default IP address for Hot standby operation
Protocol
IEC61850(GOOSE)
IP address at
Port A†
192.168.1.11
IP address at
Port B†
IP address
Not applicable
for Local PC
†Note: Address '192.168.1.11' is set as default. Setting [IPADDRESS2] will be neglected.
‡Note: '192.168.1.13' etc. can be set for the local engineering PC, if LAN for Local PC is
ready at C13.
IP setting example [RedundantMode]=Fixed
(viii)
If Fixed is set for the setting [RedundantMode], the user can apply IP addresses in the IED.
The table below shows that Port A, B, and C can have different IP addresses.
Table 10.2-5 Default IP address for Fix operation
Protocol
IEC61850(GOOSE)
IP address at
192.168.1.11
Port A†
IP address at
Not applicable
Port B
IP address at
Not applicable
for Local PC
†Note: Address '192.168.1.11' is set as default.
‡Note: An address can be set for SNTP, but it should not operate Time synchronization
with Port A and Port B, which have different IP addresses.
§Note: '192.168.1.13' can be set for the local PC, if LAN for Local PC is ready at C13.
SNTP
192.168.1.11
Not applicable
SNTP
192.168.1.11
192.168.1.12‡
Not applicable
- 524 -
6F2S1931 (0.20)
GR-TIEMS® /
MULTIPLOG®
192.168.1.11
192.168.1.13‡
GR-TIEMS® /
MULTIPLOG®
192.168.1.11
192.168.1.12§
192.168.1.13§
Centralized GRB200