Toshiba GR200 Series Instruction Manual page 615

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting of time-tagged messages
(ii)
In Time-tagged message frame in the IEC 60870-5-103 standard, event information and
status information are responded for Class 1 request from the upper system (station). The
GR-series relay can provide event information and status information by Time-tagged
message frame about the signal assigned to a Data ID of the signal list.
When the "Time-tagged message" tab is selected, the "Time-tagged message" setting
screen is displayed on the start screen.
Figure 10.4-5 Time-tagged message in the GR-TIEMS
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative
time) can be set in this screen. In one frame of Time-tagged message, the Type ID, INF,
FUN, DPI and COT must be set and the maximum 256 frames of Time-tagged message can
be set. The information number of the frame is determined by the INF setting. The most
left item "No." is only serial number and can be skipped.
Common address is linked with the address setting† in the IEC 60870-5-103 standard.
†Note: For more information, see
In the transmission format of Type ID=1 (Time-tagged message) and Type ID=2 (Time-
tagged message with relative time), customized items are shown in Table 10.4-3 and Table
10.4-4.
Table 10.4-3 Time-tagged message (Type ID=1)
Oct.
Item
1
Start
2
Length
3
Length
4
Start
5
Control field
6
Address
7
Type identification (Type ID)
8
Variable structure qualifier
9
Cause of transmission (COT)
Appendix: IEC 60870-5-103 interoperability
Value
68H
14
14
68H
08H+ACD+D
FC
1-254
Setting from the relay
1
Customized by GR-TIEMS
81H
1/9/11/12
Customized by GR-TIEMS
- 601 -
6F2S1931 (0.20)
.
Remarks
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)