Legacy IEC61850 (i.e., 61850 Editon1)
(i)
It is early edition for the IEC61850 standard. This edition is bundled in all 61850 software.
61850 Edition1 with option
(ii)
When the IED has the IEC61850 Edition1 with Option, the IED can have private object, which
can handle DataUpdate Trigger. For more information, see section 10.3.9.
61850 Edition2
(iii)
When the 61850 edition2 is available in the IED, the IED has LN LGOS, which shall be used
monitoring of GOOSE message. Note that there shall be one instance of LGOS per GOOSE
subscription for a given GOOSE source.
The user can handle LGOS with signals shown in Table 10.3-3. The signals are provided for
mapping in the 61850 Editon2. Figure 10.3-3 shows an example that they are mapped for the
LGOS.
Table 10.3-3 GOOSE message for the monitor or the diagnostic
Signals (Data ID)
305101 7400006470
305101 7400016470
...
305101 7400016470
Signal names
SUB_GOOSE_MONITOR #0
SUB_GOOSE_MONITOR #1
...
SUB_GOOSE_MONITOR #319
Figure 10.3-3 Example of Editon2 LGOS mapping
Monitor/Diagnose GOOSE Message
Monitor/Diagnose GOOSE Message
...
Monitor/Diagnose GOOSE Message
- 539 -
6F2S1931 (0.20)
Descriptions
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)