Toshiba GR200 Series Instruction Manual page 293

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Respective element IDs (i.e., 8001001172 and others) designate respective signal
monitoring points of the binary input circuits (i.e., BI1-CPL and others). Thus, the user can
handle the signals on the binary input circuit using element ID together with function ID.
When we assume that the module is at IO#1 slot, and if the user wishes to see the first circuit
signal of this module, the user can identify its signal† using the element ID (8001001172) and
the function ID of IO#1 slot‡.
†Note: The user can see the signals of the binary input circuits on the IED screen.
User interface: Monitoring-sub menu
Chapter
binary input circuits.
‡Note: Function IDs identify every IO slots. For example, IO#1 slot has been identified by
the function ID "200B001". Therefore, when the user wishes to program the signal
"BI1-CPL" at IO#1, the user should designate its signal using the function ID
"200B001" and Data ID "8001001172". On the other hand, when the signal "BI2-
CPL" at IO#2 is required to program, the user should designate that signal using
the function ID "200B002" and Data ID "8001001172". For more information with
regard to the function ID and the Data ID at IO#1, see sections 4.4.6(i), 4.4.7(i),
and others.
Setting threshold level
(i)
The voltage level "High or Low", which tells a threshold of pick up / drop off, is selectable using
the selection switch [THRES_Lvl].
Table 4.4-4 shows the threshold voltage of picking-up/dropping-off for binary inputs at the high
and low level. This also shows how to set them with the selection switch.
discusses how to see the state of the
- 279 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)