Toshiba GR200 Series Instruction Manual page 621

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Oct.
Item
11
Function type (FUN)
12
Information number (INF)
13
Short-circuit location (SCL)
17
Relative time (RET)
19
Fault number (FAN)
21
Millisecond
23
Minutes + Invalid flag (MSB)
24
Hours + Summer time flag (MSB)
25
Checksum
26
End
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Signal name / signal description
The Data ID† (Sig. No.) showing the trigger of the frame is set from the signal list. If the
setting value (signal No.) is "0", all setting items related the "Time-tagged measurand" are
disable and the frame is not provided.
The frame cannot be set to the object of GI and cannot be transmitted even though the
status of set signal changes from ON to OFF. If the metering values at the newest fault
record are transmitted as the status change frame, select the Data ID of "F.Record_DONE"
or "FAULT RECORD DONE" in the signal list of the relay.
†Note: A relevant Data ID is required to select in the signal list. The description of the
Data ID is obtained automatically on the setting.
Inverse
This setting is used to invert the logic of the signal assigned to the Data ID above. If the
frame is transmitted when the signal assigned to the Data ID is ON, leave the Inverse check
box blank. If the frame is transmitted when the signal is OFF, click the inverse check box
to be marked with "".
Type ID
Type ID=4 (Time-tagged measurand with Relative time) is fixed. In Type ID=4, the trigger
signal for the relative time should be set. For the setting, see Section 10.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the fame
out of the standard is provided, the INF should be set referring Table 10.4-3 and the
Appendix†.
†Note: For more information, see
Value
0-255
Customized by GR-TIEMS
0-255
Customized by GR-TIEMS
Customized by GR-TIEMS
Trigger condition to calculate RET is
0-65535
customized by GR-TIEMS.
Trigger condition of FAN increment is
0-65535
customized by GR-TIEMS.
0-59999
0-59+80H
0-23+80H
16H
Appendix: IEC 60870-5-103 interoperability
- 607 -
6F2S1931 (0.20)
Remarks
.
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents