Command-trip output and Command-Transfer-trip output are shown in Figure 2.4-4 to
Figure 2.4-6. If replica setting [BayDevice_CH*] = Coupler, and the busbars connected by the
coupler are bridged, tripping the coupler CB is forbidden when the setting [CoupTpBlk] =
Block. Contrarily, tripping the coupler CB is not blocked when the setting [CoupTpBlk] = Non.
When Command-trip logic and Command-Transfer-trip need to operate securely, set On
for setting [COMTP-FS]; then all Command-trip and Command-Transfer-trip will be allowed
with the Fail-safe operation (FS). On the other hand, Command-trip and Command-Transfer-
trip operate without the FS operation when Off is set for the setting [COMTP-FS].
CH1
Trip
COM.OPT-ZAX
b
COM.OPT-ZBX
COM.OPT-ZFX
From Replica
PROT-ZA_CH1

PROT-ZB_CH1

PROT-ZF_CH1

CTP-NOBLK_CH1
From Fail-Safe
FS-TRIP_CH1
Transfer trip
From Replica
TR-ZA_CH1
TR-ZB_CH1
TR-ZF_CH1
From Fail-Safe
FS-TR.TRIP_CH1
COMTP-FS
Figure 2.4-4 COMTP output signals to TRC in CH1
Setting items
Mode
Off
COMTP-FS
On
&
&
&
≥1
≥1
Off
On
Table 2.4-3 COMTP-FS setting switch
Unit
Command trip issued without FS operation
Command trip issued with FS operation
- 109 -
8320011B60
COM-TRIP_CH1
&
≥1
&
&
8620011B61
COM-TR.TRIP_CH1
&
≥1
&
&
Contents
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
To TRC
Default
Off