Scheme logic and setting
2.4.3
Figure 2.4-2 and Figure 2.4-3 show the scheme logic of the COMTP. Scheme switch [COMTP-
EN] setting On will enable to operate COMTP function for all CHs. PLC signal
COMTP_BLOCK will block the COMTP operation. Setting [TCOMTP_CH*] is provided as a
delay timer in each CH.
Setting items
Mode / range
COMTP-EN
0.00–300.00
TCOMTP_CH*
CH1
COMTP_INIT_CH1
801000EBB0
CH2
COMTP_INIT_CH2
801001EBB0
CH24
COMTP_INIT_CH24
801023EBB0
On
COMTP-EN
800000EBB5
COMTP_BLOCK
Note: Signals○
1
Table 2.4-2 COMTP setting switches
Unit
Off
Canceling COMTP operation
On
Enabling COMTP operation
s
Delayed pick-up timer for the operation
8010001BB0
&
8010011BB0
&
8010231BB0
&
&
8000001BB5
1
Figure 2.4-2 Start-up logic for COMTP
are generated for the zone evaluation of Figure 2.4-3.
a
- 107 -
Contents
8010001B60
TCOMTP_CH1
t 0
0.00-300.00s
TCOMTP_CH2
t 0
0.00-300.00s
TCOMTP_CH24
t 0
0.00-300.00s
6F2S1931 (0.20)
Default
Off
0.00
COM.OPT_CH1
COM.OPT_CH2
COM.OPT_CH24
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
1
a