Supervision of analog input data on VCTs (AI error)
9.2.14
It is possible to detect the failure of the analog to digital conversion in the VCT module† of
MainUnit and SubUnits.
†Note: See Chapter
more information. The function can operate in respective VCTs.
Error level
(i)
The default error level has been set at level 1 (Serious error
level using the [CHK_ACC:LVL]. Set On for the settings [CHK_ACC:SW]. The manufacturer
sets one (1) second to detect the failure; it is reset within a second when the failure is cleared.
Note: When the error is detected, the entire operation of the IED is stopped forcibly.
1
Error message
(ii)
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 9.2-28 Error messages provided by the supervisor in CHK_AD_CBP
Message and level
AI#1(ACC) error
AI#2(ACC) error
SUB1 AI#1 error
SUB1 AI#2 error
SUB2 AI#1 error
SUB2 AI#2 error
Error level
Table 9.2-29 Detailed information in Hexadecimal in CHK_AD_CBP
Display
area
00000001: Plus value error
00000002: Minus value error
00000004: Reverse value error
00000010: Connection error
Top
00000100: Parameter error
00000200: Parameter(2) error
row
00001000: Parameter(3) error
00010000: Parity error
00100000: Reference value error
01000000: CRC error
XXXX YYYY
Middle
XXXX: Factor error value at FPGA
row
YYYY: Factor error value
XXXX YYYY
Bottom
XXXX: Parity error value
row
YYYY: Parameter error value
Technical description: Transformer module for AC analog input
Meaning of the information
Detection of the VCT deterioration at #1 slot in MainUnit
Detection of the VCT deterioration at #2 slot in MainUnit
Detection of the VCT deterioration at #1 slot in SubUnit#1
Detection of the VCT deterioration at #2 slot in SubUnit#1
Detection of the VCT deterioration at #1 slot in SubUnit#2
Detection of the VCT deterioration at #2 slot in SubUnit#2
Serious error (Level 1)
Meaning of the detailed information
Left column
- 481 -
6F2S1931 (0.20)
), but the user can program the
1
Right column
XXXX YYYY
XXXX: Minus error value
YYYY: Plus error value
XXXX YYYY
XXXX: Factor error value at FPGA
YYYY: Factor error value
0000 YYYY
YYYY: CRC error value
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
for