Toshiba GR200 Series Instruction Manual page 767

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

PDIF class
Attribute Name Attr. Type Explanation
LNName
Data
Common Logical Node Information
OpCntRs
INC
Status Information
Str1
ACD
Str2
ACD
Str9
ACD
Op1
ACT
Op2
ACT
Op9
ACT
TmAst
CSD
Measured Values
DifAClc1
WYE
DifAClc2
WYE
DifAClc9
WYE
RstA1
WYE
RstA2
WYE
RstA9
WYE
Settings
LinCapac
ASG
LoSet
ING
HiSet
ING
MinOpTmms
ING
MaxOpTmms
ING
RstMod
ING
RsDlTmms
ING
TmACrv
CURVE
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
LN shall inherit all Mandatory Data from Common Logical Node Class
Resetable operation counter
Start
Start
Start
Operate
Operate
Operate
Active curve charactristic
Differential Current
Differential Current
Differential Current
Restraint Current
Restraint Current
Restraint Current
Line capacitance (for load currents)
Low operate value, percentage of the nominal current
High operate value, percentage of the nominal current
Minimum Operate Time
Maximum Operate Time
Restraint Mode
Reset Delay Time
Operating Curve Type
- 753 -
6F2S1931 (0.20)
(MICS Ed.1)
T M/O GRB200
M
O
N
O
Y
O
Y
O
Y
T
M
Y
T
M
Y
T
M
Y
O
N
O
Y
O
Y
O
Y
O
Y
O
Y
O
Y
O
N
O
N
O
N
O
N
O
N
O
N
O
N
O
N
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents