Toshiba GR200 Series Instruction Manual page 626

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

FUN
Function type (FUN) applied to a command response frame is set referring to Table 10.4-13.
The FUN can be set to 0 to 255. When clicking the "Change all FUNs" on the Common
setting screen, all FUNs are changed to the setting values at Common setting.
DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
"Sig off" and "Sig On" are used to set the Data ID of control object in General command.
(Hereafter, these are described as "command output signal".) "Inverse" is used to reverse
the logic when controlling the command output signal.
When the command output signal is treated as two signals (Sig Off  Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.
For example, when the DCO=Off command is received under "Inverse" no-checked,
the command output signal of "Sig Off" is controlled to "1". "Sig On" is not controlled.
Table 10.4-13
Control Scheme of Command Output Signal (Sig Off  Sig On)
"Inverse" checked
Control object
Receiving
command DCO
Off
On
When the command output signal is treated as one signal (Sig Off  Sig On), the
control scheme is shown in Table 10.4-14. For example, when the DCO=On command is
received under "Inverse" checked, the command output signals of "Sig On" and "Sig Off" are
controlled to "0". "Sig On" is not controlled.
Table 10.4-14
Control Scheme of Command Output Signal (Sig Off = Sig On)
"Inverse" checked
Control object
Receiving
command DCO
Off
On
When setting the "Sig Off", "Sig On" and "Inverse", check the specifications of the
command output signals of communication and others, and then set them.
Valid time
Checked
Signal specified
Signal specified
to Sig.off
to Sig.on
Controlled to "1"
Not controlled
Not controlled
Controlled to "1"
Checked
Signal specified
Signal specified
to Sig.off
to Sig.on
Controlled to "0"
Controlled to "1"
- 612 -
6F2S1931 (0.20)
No-checked
Signal specified
Signal specified to
to Sig.off
Sig.on
Controlled to "0"
Not controlled
Not controlled
Controlled to "0"
No-checked
Signal specified
Signal specified
to Sig.off
to Sig.on
Controlled to "1"
Controlled to "0"
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)