Logic timer switch
(v)
The LED indicator #3 can have programmable reset characteristics using scheme switch
[TIMER-SW]. Four types are available: (1) dwell type, (2) delay type, (3) latch type, and (4)
instantaneous type:
Instant type
When required not to have the below characteristics (v)-2, (v)-3, and (v)-4, the user should set
Off for the scheme switch [TIMER-SW].
Delay type
If the user requires lighting the LED indicator with a delayed characteristic, the user should
set Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer].
Dwell type
For instance, if the user requires lighting the LED indicator as a one shot pulse, the user
should set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using
setting [Logic timer]. If the input signals received have a shorter duration than the set value
in the setting [Logic timer], the pulse width will be equal to the setting value. On the other
hand, if the duration of the input signals are longer than that of the set value, the pulse width
will be equal to the width of the input signals.
Latch type
If the user requires lighting the LED indicator to be removed by a reset signal, the user should
set Latch for scheme switch [TIMER-SW]; the user should set the Data ID of the reset signal
for setting [Reset signal]. Since lighting the LED indicator is cleared with the Data ID, the
user should determine the Data ID from other functions. The Data ID is designated by the
signal monitoring point for each function and the user should set the [Reset signal] setting.
Selection of the LED color
(vi)
For the LED indicator #3, color selection of either RED/GREEN/YELLOW is possible using the
setting [Color].