2. BIO signals with regard to CB, DS, and trip signals
2-1. CHs at feeders
(1)Binary inputs
Requiring input conditions are as follows.
-DS contacts
-CBF start signals by the line-protection
-(*1)CB contacts are not required, so they are not injected.
(2)Binary output
Recommending output signals are as follows.
-BP trip signal (=DIF trip signal)
-CBF trip signal (=CBF re-trip and CBF zone-trip signal)
-CBF TR signal (=CBF transfer trip signal)
Feeder
Bus-A
Bus-B
Note: Toshiba recommends outputting it, although the preceding relay (GRB100 series)
2
did not issue the CBF TR signal.
DS
DS
-A
-B
P
DS-A
CB
CH-W
P
DS-B
P
CBF starts
by the line-protection
2
mainly for CH-W
BIO5 A
(+)
1
BI1
(-)
2
(+)
3
BI2
(-)
4
N/O contact
(+)
5
BI3
N/C contact
(+)
6
BI4
(-)
7
N
N/O contact
(+)
8
BI5
N/C contact
(+)
9
BI6
(-)
10
N
(+)
11
BI7
(+)
12
BI8
(+)
13
BI9
(-)
14
N
15
BO1
16
17
BO2
18
21
BO3(SF)
22
23
BO4(SF)
24
25
BO5(SF)
26
27
BO6(SF)
28
29
BO7(SF)
30
31
BO8(SF)
32
35
37
36
BO9
38
- 744 -
6F2S1931 (0.20)
P
BP trip
(DIF trip)
P
CBF trip
(Re-trip and Zone-trip)
P
CBF TR trip
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)