Toshiba GR200 Series Instruction Manual page 201

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Blocking coupler (CoupTpBlk)
2.8.2
The user can block the operation of couplers using CoupTpBlk setting. If Block is set for
CoupTpBlk, the CB tripping on the coupler will be blocked when a fault occurs on the busbar
system during a busbar-bridge operation.
Settings of CBP REPRICA (Function ID: 4F0B01)
Setting item
Misc.
CoupTpBlk
Unit
Range
s
Coupler trip block under busbar bridge
Non / Block
condition
- 187 -
6F2S1931 (0.20)
Contents
setting value
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
Default
Notes
Block

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents