Mapping signals in signal list to Logical Nodes
(iv)
The user can add or modify signal mapping to the LN variable. The following section describes
how to modify the mapped data if the user wants to add signals, which are sent using Report
or GOOSE.
Edit Mapping Data
1. Search the signal to be sent from the Signal List window as shown in Figure
10.3-14.
2. Drag and Drop the selected signal to the logical node variable.
Note: To optimize the performance of the IED, "Period" should be 100 if the signal is not
required to be sent immediately.
The user should map a quality signal (i.e., Qual_Validity, U16_00, or U16_01)
should be mapped to "q" with Period=100.
The user should map a time signal (i.e., SYS_TIME) should be mapped to "t".
Export / Import Mapping Data
The user can export mapped data in the CSV file; the user can edit the exported
CSV file by the MS-Excel® and import back into the GR-TIEMS. Figure 10.3-15
shows the export / import options.
Figure 10.3-15 Export / Import mapping data
Mapped data
Drop
Figure 10.3-14 Signal mapping
- 551 -
6F2S1931 (0.20)
Drag
Signals
Export Mapping Data
Import Mapping Data
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)