Toshiba GR200 Series Instruction Manual page 806

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

15.
PIXIT FOR TIME AND TIME SYNCHONISATION MODEL
ID
Ed
What time quality bits are supported (may be
set by the IED)
Tm1
1
Describe the behavior when the time server(s)
ceases to respond
Tm2
1,2
What is the time server lost detection time
How long does it take to take over the new time
Tm3
1,2
from time server
1,2 When is the time quality bit "ClockFailure" set RTC is out-of-order
Tm4
When is the time quality bit "Clock not
Synchronized" set
Tm5
1,2
Is the timestamp of a binary event adjusted to
Tm6
-
the configured scan cycle
Does the device support time zone and daylight
Tm7
1
saving
Which attributes of the SNTP response packet
are validated
Tm8
1,2
Do the COMTRADE files have local time or
Tm9
1,2
UTC time and is this configurable
Description
- 792 -
Value / Clarification
Y
LeapSecondsKnown
N
ClockFailure
Y
ClockNotSynchronized
On one time server: IED tries to
synchronize with another time
server.
On all time servers:
The quality attribute
"ClockNotSynchronized" will be set
to TRUE.
The lost detection time depends on
the network condition.
10 seconds
It depends on the condition of
synchronization. Typically from 1 to
10 minutes.
Deprecated
Yes for both.
Y
Leap indicator not equal
to 3?
N
Mode is equal to SERVER
N
OriginateTimestamp is
equal to value sent by the
SNTP client as Transmit
Timestamp
Y
RX/TX timestamp fields
are checked for
reasonableness
Y
SNTP version 3 and/or 4
N
other (describe)
UTC
Not Configurable
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
(PIXIT Ed.1&Ed.2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200