Maximum number for recording disturbance phenomena
(v)
Note that the maximum number for recording the disturbance phenomena depends on the
recording time and the sampling rate. Table 7.3-1 illustrates the maximum number in
Software '30 and 32'; the disturbance recorder can have 33 phenomena when settings [Record
Time] =1 and [Sampling Rate] =7.5°, provided that the IED runs for 50Hz system. The user
can check the maximum recording number on the IED screen (See Figure 7.3-2).
Table 7.3-1 Max number depending on time settings for Software = '30', '32' and '34'
Recording
Setting [Sampling Rate]=50Hz sys.
period set with
[Record Time]
1 sec.
3 sec.
5 sec.
10 sec.
Table 7.3-2 Max number depending on time settings for Software = '31' and '33'
Recording
Setting [Sampling Rate]=50Hz sys.
period set with
[Record Time]
1 sec.
3 sec.
5 sec.
10 sec.
Number of logical signals and kinds of analog quantities
(vi)
The disturbance recorder can hold the traces of logic signals during the recording time. Using
settings [Binary Signal*], the user can select 256 logic signal arbitrary. The logic signals that
the user has selected should be termed with user's preferred names using settings [Binary
Sig.Name*]. Table 7.3-3 etc. tabulate the default settings.
About a hundred analog quantities are also recorded as disturbance phenomena.
Max. recording number for Disturbance phenomena
7.5°
15°
33
64
11
22
6
13
3
6
Max. recording number for Disturbance phenomena
7.5°
15°
36
68
12
24
7
14
4
7
- 371 -
Setting [Sampling Rate]=60 Hz sys.
7.5°
27
9
5
2
Setting [Sampling Rate]=60 Hz sys.
7.5°
30
10
6
3
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
15°
53
18
11
5
15°
60
20
12
6