Advertisement

Binary IO module (BIO)
Binary IO modules are provided to output/input a command for external gears. The user needs
to connect with the external ones using via IED rear terminals. Table 4.4-1 shows the number
of input and output circuits.
Table 4.4-1 Number of input and output circuits
Number of
Module
input
#
name
circuits
1
BI1A
18
2
BO1A
0
3
BIO5A
9
Note:
One of two voltages can be applied for the binary IO modules: 48Vdc (24 to
1
60) and 220Vdc (110 to 250). The DC voltage, supplied to the IED,
determines the selection of voltage type. Hence, the user is not allowed to
have different voltage type combination.
Note:
For the structure and the number of binary IO modules, see section 4.4.5.
2
Note:
Fart and Hybrid types are not provided in GRB200 series.
3
Number of output circuits
Fast
Semi-fast
operating
operating
4
0
6
6
- 275 -
1
2
Auxiliary
Hybrid
4
(Normal)
0
12
2
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Form C
0
0
1