Toshiba GR200 Series Instruction Manual page 979

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Binary Inputs
Input circuit DC voltage
Capacitive discharge immunity
Maximum permitted voltage
Power consumption
Binary Outputs
Semi-fast operating contacts
Make and carry
Break
Operating time
Auxiliary contacts
Make and carry
Break
Operating time
Durability
Measuring input capability
Full scale
Standard current input
Voltage input
Sampling rate
Frequency response
24/48/60Vdc
(Operating range: 19.2 – 72Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Note: Pick-up setting is available in BI2 (Setting range: 18V
to 222V)
10μF charged to maximum supply voltage and discharged
into the input terminals, according to ENA TS 48-4 with an
external resistor
72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
 0.5W per input at 220Vdc
8A continuously
30A, 240Vdc for 1s (L/R=5ms)
0.1A at 250Vdc
(L/R=40ms)
0.2A at 125Vdc
(L/R=40ms)
Typically 6 ms
8A continuously
30A, 240Vdc for 1s (L/R=5ms)
0.1A at 250Vdc
(L/R=40ms)
0.2A at 125Vdc
(L/R=40ms)
Typically 8 ms
≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
≥ 60A (1A rating) or 300A (5A rating)
≥ 200V
48 samples / cycle
< 5% deviation over range 16.7Hz to 600Hz
- 965 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)