Toshiba GR200 Series Instruction Manual page 646

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

[A] Exception status (Function code: 0x07)
The Exception status function is provided in the IED (slave). Depending on
the same cases of the substation computer request (master), the IED (slave)
can return its own status. The status information is eightfold 1-bit, and the
user can set it arbitrarily by the GR-TIMES engineering.
[B] Diagnostic register (Function code: 0x08)
The Diagnostics register is provided in the IED (slave). By the demand of the
substation computer (master), the IED (slave) can return its own information.
The information is sixteen-hold 1-bit. Some items are mapped by the
manufacture.
[C] Report server ID (Function code: 0x11)
This is designed for that an IED can return its own IED model and type.
[D] Encapsulated Interface Transport (Function code: 0x2B)
This is designed for that an IED can return its own product information.
GR200-series IED supports the product information in Table 10.5-5.
Table 10.5-5 Encapsulated Interface Transport Type and Object
Type
Id
0(0x00)
01
1(0x01)
(Basic)
2(0x02)
4(0x04)
02
5(0x05)
(Regualr)
6(0x06)
03
129(0x81)
(Extended)
Object
Name
Vendor Name
Product Code
Major Minor Revision
Product Name
Model Name
User Application Name
-(Private object)
- 632 -
6F2S1931 (0.20)
Description
"TOSHIBA"
Hardware ordering code
"00"
IED Type
Software ordering code
"PROTECTION RELAY"
Name and version number
about the CPU Software
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)

Hide quick links: