Toshiba GR200 Series Instruction Manual page 638

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Communication
10:48
1/7
LAN
>
USBCOM
>
RS485
>
SLAVE PROTOCOL
>
IEC61850
>
IEC103 SLV
>
MODBUS
>
Figure 10.5-3 Selection of Modbus on the Commination setting menu
Note; This sample menu illustrates how to select the Modbus, so that we discuss neither
the inclusion of IEC61850, IEC103, and DNP3.0, nor the selection of those
protocols. See Figure 10.1-1 to check the inclusion of the protocols in the IED.
The Modbus slave operation can be switched off briefly if the setting [MODBUS_BLK] = On.
Communication
10:48
1/7
LAN
>
USBCOM
>
RS485
>
SLAVE PROTOCOL
>
IEC61850
>
IEC103 SLV
>
MODBUS
>
Figure 10.5-4 Blocking the Modbus operation (LCD setting menu)
Modbus interface
10.5.3
When the Modbus protocol is provided in the IED†, the measurement and status information
of the IED are transferred to the substation computer by that protocol. It is executed with
message frames from the substation computer message (called "Master query"); then, the data
(called "Slave response") is transferred to the substation computer from the IED. The message
frames can include the following data:
Measurement:
Event status:
Time:
†Note: The GR200-series IEDs do not support to applications (control functions, such as,
DPOS etc.) in the Modbus protocol.
SLAVE PROTOCOL
10:48
1/1
Slave Protocol
+
Modbus
MODBUS
10:48
1/3
MODBUS_BLK
+
Off(On)
MODBUS ADDR
+
2
MODBUS_SELECT
+
TCP
Current quantities, voltage quantities, etc.
Events, fault modes, counters, etc.
Clock setting /synchronization
- 624 -
6F2S1931 (0.20)
SLAVE PROTOCOL
10:48
IEC61850†
IEC103†
DNP3.0†
Modbus
Press
ENTER
key
, , , 
Press
to
set [MOSBUS BLK]=On
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)