Toshiba GR200 Series Instruction Manual page 620

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting for time-tagged measurands
(iii)
For Time-tagged measurand frame in the IEC 60870-5-103 standard, event information
supplemented with numerical information are responded for Class 1 request from upper
system (station). The GR200-series relay can provide event information, which is converted
the numerical information in metering table according to user setting weight, by using
Time-tagged measurand frame about the signal assigned (i.e., the Data ID).
When the "Time-tagged measurand" item is selected on the GR-TIEMS, the setting
screen is displayed.
Type ID=4 (Time-tagged measurand with relative time) can be set in this screen. In
one frame of Time-tagged measurand, the INF, FUN, Sig No., Rev, COT and SCL must be
set and the maximum eight frames of Time-tagged measurand can be set. The information
number of the frame is determined by the INF setting. The most left item "No." is only serial
number and can be skipped.
Common address is linked with the address setting† of the relay.
†For more information, see
In the transmission format of Type ID=4 (Time-tagged measurand with relative time),
customized items are shown in Table 10.4-9.
Table 10.4-9
Oct.
Item
1
Start
2
Length
3
Length
4
Start
5
Control field
6
Address
7
Type identification (Type ID)
8
Variable structure qualifier
9
Cause of transmission (COT)
10
Common address of ASDU
Figure 10.4-6 Time-tagged measurands
Appendix: IEC 60870-5-103 interoperability
Time-tagged measurand with relative time (Type ID=4)
Value
08H+ACD+DFC
1-254
1/7/11/12
1-254
- 606 -
68H
20
20
68H
Setting from the relay
4
81H
Customized by GR-TIEMS
Linked with Address setting
6F2S1931 (0.20)
.
Remarks
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)