Toshiba GR200 Series Instruction Manual page 227

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Figure 3.6-11 LN editing for SBO mode (for example)
Defining DIR mode
Figure 3.6-12 exemplifies the LEDR logic node saved as LLN0. In the DIR mode, the following
three items should be selected using GR-TIEMS:
Figure 3.6-12 LN editing for DIR mode (for example)
Mapping output data
(ii)
The user should group the OPTR signals with regard to GOOSE and Report; the user should
map them for IEC61850 communication using GR-TIEMS. Figure 3.6-13 illustrates how to
map a signal for IEC61850 communication; it indicates that the signals for the LEDR function
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice "operate-once")
ctlmodel (choice "SBOes or SBOns")
†"sboClass" can be found by scrolling down.
Oper
origin
ctlmodel (choice "DOes or DOns" )
- 213 -
6F2S1931 (0.20)
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)