apply the signal at other connection point (PLC#4; i.e., DEV01_P1_COMMAND). We should
assume the PLC#3 and PLC#4 as PLC#1 and PLC#2 in Table 4.9-2. Note that the user should
set PLC for scheme switch [TPOS01-LGP1EXOT].
Input
Command "PLC-P1-Control" requiring ILK check
(PLC#3 connection point)
513001 800401EE31
DEV01_P1_INTERLOCK
Command "PLC-P1-Control" not requiring ILK check
(PLC#4 connection point)
513001 800401EE30
DEV01_P1_COMMAND
ILK† condition ("P1") passed
TPOS1-P1
User configurable condition
(PLC#1 connection point)
513001 800401EE56
TPOS01IN_TMP_27
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-39 Operate P1- control using the PLC function in TPOS01
†Note: The ILK function can provide the criteria for operation for "P1" control.
‡Note: An "operate condition" signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition" programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
"operate-condition" to the logic shown in Figure 4.9-39 using connection point #1
"User configurable condition" That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use "TPOS01IN_TMP_27".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
Note: To identify the input and output signal-points of the P1-control in the other TPOS
††
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
Operate Cmd.
with ILK
condition
&
Operate Cmd.
without ILK
condition
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP1EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P1EC_OK_CSF"
(513001 8004011E7E)
- 947 -
"
TPOS01_P1EC_OK_CS"
(5130018004011E81)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1914 (0.49)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P1EX_BO"
(5130018104011DD0) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
"
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
[TPOS01-RST]
0
t
1.0s- 100.0s
Operate Failed
††
GRL200 (Soft 033 & 037)
"
"