Toshiba GR200 Series Instruction Manual page 699

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command "Local-Closing-Control"
ILK† condition ("Closing") passed
DPSY01-Close
ILK† bypassing
From SYNCHK
SYNC01-SLD_VCS‡‡
(560001 840B011F58)
SYNC‡‡ bypassing
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
"Automatic sequence control function (AQEQ)§" in progress
ASEQ_MULTI_SEL
Figure 4.2-6 Select 'Closing' on the front panel in DPSY01
†Note: The ILK function provides the operation criterion for "On". For testing, nullifying
the ILK function is possible using "Interlock bypassing". "Interlock bypassing" is
indicated by the status "ICB" in a software switch controller (SOFTSW).
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
Note: To identify the output signals of the DPSY02 logic, see Table 4.2-10.
††
Note: The SYNDIF function provides the synchronism criteria for "Closing". For
‡‡
testing, nullifying the SYNDIF function is possible using "Synchro-check
bypassing". "Synchro-check bypassing" is indicated by the status "SCB" in the
SOFTSW.
Output signal to BO
When the signal "select condition" is true, the DPSY01 function can issue a "Selection success"
signal at the output-point "DPSY01_OSL_BO_CSF".
Note: The signal "DPSY01_OSL_BO_CSF" is the same as the signal shown in Figure
4.2-2. If the "Local-Closing-Control" signal is not true, the DPSY01 function
returns to the "Wait for a command" stage.
DPSY01 function (Function ID: 511001)
For SBO operation
Selection command
with ILK† condition
For DIR operation
Operation command
with ILK† condition
1≥
ICB_STATE
1≥
SCB_STATE
[DPOS01-CTRAHMI]
SBO
Select condition‡
Selection logic in DPSY01
&
SBO
&
DIR
- 676 -
6F2S1914 (0.49)
1≥
&
To "Wait for a next
To BO connection
DPSY01_OSL_BO_FLG"
(511001 8602011DC6)
0
t
Selection "Closing"
0.1s
Timer§§
To "Wait for a command"
0
t
0
t
Selection "Failed"
0.0 to 5.0 s
0.6s
††
GRL200 (Soft 033 & 037)
Output
command"
.