Communication bits for OSTV
2.37.5
When the function 'Out of step tripping by voltage (OSTV)' operates, the area of the 'V 0 ' is used
for the communication for the OSTV function in place of sending the zero-sequence voltage.
For more information about the OSTV function, see Chapter
tripping by voltage
Usage of sub-communication channel
2.37.6
Figure 2.37-6 shows the connection and monitoring points in the COM3_1bit to COM3_8bit of
Wide (N=3) communication. For example, when the user wishes to send a bit-signal using the
COM3_1 sub-channel, the user should connect the signal with PLC connection point "COM3-
1_S". On the other hand, when the user wishes to retrieve a bit-signal from the COM3_1 sub-
channel of the remote terminal-1, the user should use PLC monitoring point "COM3-1_R1".
With regard to the reception from the remote terminal-2, other PLC monitoring points are
provided. Entire PLC connection points and monitoring points for the sub-communication
channels are shown later.
a. PLC connection points
800214EBB0
COM3-1_S
810214EBB1
COM3-2_S
820214EBB2
COM3-3_S
830214EBB3
COM3-4_S
840214EBB4
COM3-5_S
850214EBB5
COM3-6_S
860214EBB6
COM3-7_S
870214EBB7
COM3-8_S
b. PLC monitoring points
as to the reception
from remote terminal 1
Figure 2.37-6 Connection and monitoring points for COM3 (1 to 8 bits)
Setting of open terminal detection
2.37.7
The open terminal detection (OTD) function is provided and a set of Off is placed for scheme
switch [OTD] as a default.
.
COM3 (8bits)
1 2 3 4 5 6 7 8
8710051CF8
COM3-8-R1
8610051CF7
COM3-7-R1
8510051CF6
COM3-6-R1
8410051CF5
COM3-5-R1
8310051CF4
COM3-4-R1
8210051CF3
COM3-3-R1
8110051CF3
COM3-2-R1
8010051CF2
COM3-1-R1
- 514 -
Relay application: Out of step
c. PLC monitoring
points as to the
COM3 (8bits)
reception from
1 2 3 4 5 6 7 8
remote terminal 2
6F2S1914 (0.49)
8710071C91
COM3-8-R2
8610071C90
COM3-7-R2
8510071C8F
COM3-6-R2
8410071C8E
COM3-5-R2
8310071C8D
COM3-4-R2
8210071C8C
COM3-3-R2
8110071C8AB
COM3-2-R2
8010071C8A
COM3-1-R2
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading