SPAR logic – settings (TSPAR1, TRR1)
(viii)
The SPAR logic for CB#1 and CB#2 is illustrated in Figure 2.34-18. The 'ARC1_SPAR' signal
is generated when the SPAR condition is appeared in the Condition logic; the SPAR logic has
the dead timer [TSPAR1] provided to delay issuing a reclose command, which turns into 'ARC1
SHOT1' signal later. The user should set the [TRR1] to have the coordination with the
[TSPAR1]; the final trip will occur when 'ARC1-S1 TRR' signal is present. The SPAR logic for
CB#2 is similar to the one for CB#1.
Always '1'
Initiation
ARC1 IN-PROG
ARC1-S1 IN-PROG
Condition of CB#1
ARC1_SPAR_COND
Always '1'
ARC2-S1 IN-PROG
Condition of CB#2
ARC2_SPAR_COND
Note: Settings [TSPAR1_SUB] and [TSPAR2_SUB] are not required as in the default.
&
800001EBB9
800001EBBA
800001EBBB
800001EBBC
&
800002EBB9
800002EBBA
800002EBBB
800002EBBC
Figure 2.34-18 ARC1 SPAR and ARC2 SPAR
- 453 -
TSPAR1
t
&
SPAR1_START
0.01 – 300.00 s
SPAR1_COND
TSPAR1_SUB
t
&
SPAR1_SUB_START
0.01 – 300.00 s
SPAR1_SUB_COND
TSPAR2
t
&
SPAR2_START
0.01 – 300.00 s
SPAR2_COND
TSPAR2_SUB
t
&
SPAR2_SUB_START
0.01 – 300.00 s
SPAR2_SUB_COND
TRR1
t
0
ARC1-S1 TRR
0.01 – 310.00 s
TRR2
t
0
ARC2 TRR
0.01 – 310.00 s
6F2S1914 (0.49)
Issuing for CB#1/CB#2
8000011B63
0
ARC1_SPAR
&
≥1
0
&
8000021B63
0
ARC2_SPAR
&
≥1
0
&
To TRC
ARC1-FT
CB1_94TT
ARC2-FT
CB2_94TT
GRL200 (Soft 033 & 037)