Toshiba GR200 Series Instruction Manual page 188

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

ZG (Function ID: 431001)
Setting items
Z2G-LPBlk
Z2G-TPMD
Z2G-ARCBlk
Z2G-OCFS-EN
OCF2G
Z2G-SOTF
Z3G
Z3G-Dir
Mho
Z3G-Mho.Angle
Z3G-
Mho.Reach
Z3G-MhoX.EN
Z3G-X.Reach
Z3G-MhoR.EN
Z3G-R.Angle
Z3G-R.Reach
Z3G-DX.Angle
Z3G-
MhoDX.EN
Quad
Z3G-X.Reach
Z3G-R.Angle
Z3G-R.Reach
Z3G-DX.Angle
Z3G-DR.Angle
I0K
Z3G-Krs
Z3G-Kxs
Z3G-Krm
Z3G-Kxm
TZ3G
Output
Z3G-EFL
Z3G-MPFBlk
Z3G-PSBBlk
Z3G-LEBlk
Z3G-LPBlk
Z3G-TPMD
Z3G-ARCBlk
Z3G-OCFS-EN
OCF3G
Z3G-SOTF
Z4G
Z4G-Dir
Mho
Z4G-Mho.Angle
Range
Unit
1A rating
5A rating
Non / Block
- Z2G leading phase operation block
Z2G trip mode, phase segregated trip or 3-
1P / 3P
-
phase trip
Non / Block
- Autoreclose execution block by Z2G-trip
Off / On
- Fail-safe OC for Z2G-trip
0.10 -
0.02 - 5.00
A Fail-safe OC operation level for Z2G-trip
25.00
Off / On
- SOTF using Z2G
Forward / Reverse /
- Z3G direction to protect
NonDir
30 - 90
deg Z3G mho characteristic angle (for Mho)
0.10 -
0.01 -
- Z3G mho reach (for Mho)
500.00
100.00
Off / On
- Z3G reactance reach use or not (for Mho)
0.10 -
0.01 -
- Z3G reactance reach
500.00
100.00
Off / On
- Z3G resistive reach use or not (for Mho)
30 - 90
deg Z3G resistive reach characteristic angle
0.10 -
0.01 -
- Z3G resistive reach
500.00
100.00
0 - 60
deg Z3G directional-X characteristic angle
Z3G directional-X characteristic use or not (for
Off / On
-
Mho)
0.10 -
0.01 -
- Z3G reactance reach
500.00
100.00
30 - 90
deg Z3G resistive reach characteristic angle
0.10 -
0.01 -
- Z3G resistive reach
500.00
100.00
0 - 60
deg Z3G directional-X characteristic angle
Z3G directional-R characteristic angle (for
0 - 60
deg
Quad)
0 - 1000
% Zero phase current factor, Self line R0/R1
0 - 1000
% Zero phase current factor, Self line X0/X1
Zero phase current factor, Adjacent line
0 - 1000
%
R0m/R1
Zero phase current factor, Adjacent line
0 - 1000
%
X0m/X1
0.00 - 100.00
s Z3G operation delay time
EFL operation condition used or not for Z3G
Off / On
-
operation
Non / Block
- Z3G operation block or not in multi phase fault
Non / Block
- Z3G operation block or not by PSB detection
Non / Block
- Load encroachment enable
Non / Block
- Z3G leading phase operation block
Z3G trip mode, phase segregated trip or 3-
1P / 3P
-
phase trip
Non / Block
- Autoreclose execution block by Z3G-trip
Off / On
- Fail-safe OC for Z3G-trip
0.10 -
0.02 - 5.00
A Fail-safe OC operation level for Z3G-trip
25.00
Off / On
- SOTF using Z3G
Forward / Reverse /
- Z4G direction to protect
NonDir
30 - 90
deg Z4G mho characteristic angle (for Mho)
- 165 -
6F2S1914 (0.49)
Contents
GRL200 (Soft 033 & 037)
Default
Note
1A
5A
Non
3P
Block
Off
0.20
1.00
Off
Forward
85
40.00
8.00
Off
40.00
8.00
Off
75
25.50
5.10
30
Off
40.00
8.00
75
25.50
5.10
30
5
100
100
0
0
0.40
On
Non
Non
Non
Non
3P
Block
Off
0.20
1.00
Off
Reverse
85