[DPSY01-PLSM], the output period of the signal is defined by the setting applied
to [DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
Note: To identify the input and output signal-points in the DPSY02 logic, see Table
††
4.2-3 and Table 4.2-4 for PLC#1 to PLC#4, Table 4.2-15 and Table 4.2-16 for
PLC#1/#2 for user configurable conditions, Table 4.2-20, and Table 4.2-21 for the
outputs.
Note: The "Operate failed" signal is issued when a state-change remains undetected
‡‡
following expiration of the setting applied to timer [DPSY01-RST].
Output signal to BO
The DPSY01 function, in Figure 4.2-28, can issue an "Operate" signal at output point
"DPSY01_OEX_BO", when the DPSY01 function determines that the "PLC-Closing-Control"
signal is true.
Receiving "operate command Open" using PLC logic
(vi)
Figure 4.2-29 depicts the reception of the operate command for Open using the PLC function.
These input and output signals and the process are highlighted in the figure below.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing with the PLC
function
Select command Open with the PLC function
Figure 4.2-29 Outline of operate command for Open
Input signal from the PLC function
Figure 4.2-30 depicts the operate logic when an "Operate command Open (PLC-Open-Control)"
signal is generated by the PLC function. There are two points for reception of this command
signal, unlike the signal ("Operate command Closing (PLC-Closing-Control)". That is, if an
interlock check is required, apply the signal at connection point ("PLC#4: i.e.,
DEV01_OP_INTERLOCK"). If, on the other hand an interlock check is not required, apply the
signal at connection point ("PLC#5: i.e., DEV01_OP_COMMAND"). PLC#1 and PLC#2 shown
in Table 4.2-4 should be treated as PLC#3 and PLC#4 here.
Wait for a next command
Operate command Closing from the remote-end
Operate command Open from the remote-end
Operate command Closing from the local-end
Operate command Open from the local-end
Operate command Closing with the PLC function
Operate command Open with the PLC function
Operate logic
PLC logic programmed
by the user
- 700 -
6F2S1914 (0.49)
Success
Operation
Signal output
decision
Do nothing
Failed
GRL200 (Soft 033 & 037)