Toshiba GR200 Series Instruction Manual page 966

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Input
Command Local-P2-Control"
513001_7004016D08
DEV01_CONTROL_REQ
ILK† condition ("P2") passed
TPOS1-P2
ILK† bypassing
ICB_STATE
User configurable condition (PLC#3 connection point)
513001 810401EE57
TPOS01IN_TMP_28
ASEQ function§" is in progress
ASEQ_MULTI_SEL
User configurable condition
(PLC#2 connection point)
513001 820401EE5E
TPOS01IN_TMP_38
Figure 4.9-35 Operate 'P2-control' on the front panel in TPOS01
†Note: The ILK function can provide the operation criteria for "P2" control.
‡Note: An "operate condition" signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative "operate-condition is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative "operate-condition" can be connected to the to the above logic using
connection point #3 "User configurable condition" That is, set the [TPOS01-
LGCTRCON] to PLC and using " TPOS01IN_TMP_28".
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The "Operate failed" signal is issued when the state-change is not detected until
after reaching the time set by the [TPOS01-RST].
§§Note: The signal "TPOS01-PIEX-BO" is issued when Fixlogic is set for the [TPOS01-
LGP1EXOT]. The "Operate completed" signal can also be issued from the logic
programmed by the user in place of the logic shown in Figure 4.9-26 . The user-
programmed logic is connected internally to the signal "operate completed", hence
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
"
TPOS01_P2EC_OK_CSF"
(513001 8004011E7F)
Operate Cmd.
with ILK
condition
&
Operate Cmd.
without ILK
condition
1≥
[TPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[TPOS01-LGP2EXOT]
Fixedlogic
[TPOS01-PLSM]*
Var
Fix
Detection of state-change in a device
"TPOS01_P2EC_OK_CSF"
(513001 8004011E7F)
- 943 -
"
TPOS01_P2EC_OK_CS"
(513001 8304011E82)
1≥
1≥
&
&
&
&
&
1≥
&
&
6F2S1914 (0.49)
Output
[TPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
To BO connection
"TPOS01_P2EX_BO"
(513001 8204011DD3) §§
&
Assign to BOs
To "Wait for a command"
"
TPOS01_EX_CMP
(513001 8004011E93)
Operate Completed
"
TPOS01_EX_FFL
[TPOS01-RST]
(513001 8604011E91) ‡‡
0
t
1.0s- 100.0s
Operate Failed
††
GRL200 (Soft 033 & 037)
"
"